: Public Class
Created: 12-Apr-11 15:58:52
Modified: 12-Apr-11 15:58:52
Project:
Advanced:
PhaseTapChangerTabularPoint describe each tap step in the curve.
Attribute
Public <a href="../../EA1/EA47.htm">AngleDegrees</a>
  angle

Details:
GUIDBasedOn={7D40B9B7-F9FC-45a0-A7CE-28D3DC182E4D}
Notes: The angle difference in degrees.
Public <a href="../../EA1/EA58.htm">PerCent</a>
  b

Details:
GUIDBasedOn={434B9506-8066-4662-B988-DFE0241657E7}
Notes: The magnetizing branch suseptance deviation in percent of nominal value. The actual suseptance is calculated as follows:<br /></p><p>calculated magnetizing suseptance = b(nominal) * (1 + b(from this class)/100).   The b(nominal) is defined as the static magnetizing suseptance on the associated power transformer end or ends.  This model assumes the star impedance (pi model) form.<br /></p>
Public <a href="../../EA1/EA58.htm">PerCent</a>
  g

Details:
GUIDBasedOn={CE873A23-0FC9-459a-9B90-D4856F972966}
Notes: The magnetizing branch conductance deviation in percent of nominal value. The actual conductance is calculated as follows:<br /></p><p>calculated magnetizing conductance = b(nominal) * (1 + g(from this class)/100).   The g(nominal) is defined as the static magnetizing conductance on the associated power transformer end or ends.  This model assumes the star impedance (pi model) form.<br /></p>
Public <a href="../../EA1/EA58.htm">PerCent</a>
  r

Details:
GUIDBasedOn={06D12696-62AB-43b1-808B-A07D788BB0ED}
Notes: The resistance deviation in percent of nominal value. The actual reactance is calculated as follows:<br /></p><p>calculated resistance = r(nominal) * (1 + r(from this class)/100).   The r(nominal) is defined as the static resistance on the associated power transformer end or ends.  This model assumes the star impedance (pi model) form.<br /></p>
Public <a href="../../EA1/EA44.htm">Integer</a>
  step

Details:
GUIDBasedOn={BCAC6926-A121-468e-AB4E-8990F5CE849E}
Notes: The tap step.
Public <a href="../../EA1/EA58.htm">PerCent</a>
  x

Details:
GUIDBasedOn={D5F20C76-93B3-4d42-97BF-8AC69A8B53AE}
Notes: The reactance deviation in percent of nominal value. The actual reactance is calculated as follows<br /></p><p>xcal = xnom(1 + x/100).<br /></p>
Element Source Role Target Role
PhaseTapChangerTabular
Class  
Name: PhaseTapChangerTabular
 
Name: PhaseTapChangerTabularPoint
 
Details:
 
Tag Value
GUIDBasedOn {D2A2282D-3EBD-47ea-8339-B78FEC97977F}
Details: